Industrial unit at Loyang
New and relocated units for a construction company, with the condensers raised onto an elevated ledge.
New air-conditioning across a factory's server room, logistics office, isolation room and office, with the server room on two units that share the duty and both start if the room warms, and the existing VRF plant put right.

A manufacturer needed new air-conditioning in four areas over three floors, and a server room that stays cool without anyone watching it. Its existing VRF plant was also short of refrigerant and had a failing fan.
Two ceiling-suspended units for the server room, alternating duty every 12 hours so they wear evenly, with the existing panel modified to start both if the room passes 20°C. Wall-mounted units for the logistics office and a multi-split for the isolation room and the office. For the VRF plant: recover the gas from the decommissioned unit, charge the other, swap in the decommissioned unit's working fan, and check every condensing unit so parts in poor condition can be watched or replaced before they fail.
The server room has a standby unit that takes over by itself, and both run if the room warms. Four areas run on new equipment, and the VRF plant has a written list of what to watch.