F&B

Café at Balestier

A cat interaction room with more than 30 cats, kept fresh for the café around it. We worked out the air changes the room needs and rebuilt how it is ventilated.

Illustration, not a drawing of the site

The brief

The café wanted its cat interaction room, home to more than 30 cats, to stay fresh for customers, and had already tried air purifiers. It also needed more cooling as the floor was reconfigured.

What we found

  • Purifiers clean the air in a room but do not replace it. A room with this many animals needs a steady number of air changes, and it had no extract fan of its own.
  • Its air could only leave through a duct section shared with the storeroom, so it lingered in the room.
  • The room is cooled by a split unit, so the extract rate had to be balanced against it: enough air changes to keep the room fresh, without pulling so much that it could not hold its temperature.
  • The restroom extract fan was also due for replacement, and a drainage pipe outside the staff toilet needed fixing.

What we recommended

Audit the existing ventilation and rebuild it around the cat room: a vent through the false wall into the storeroom, a 4-inch EC centrifugal fan pulling from it into the existing duct outlet, the old shared duct section sealed so air can only go one way, and the vent enlarged from 150 to 190 mm to suit. Add an in-line silencer, because a fan people can hear gets switched off. Replace the restroom fan with the same model.

The work

  • Air change requirement worked out for the cat room and balanced against its split air-conditioning
  • New vent in the false wall between the cat room and the storeroom, enlarged from 150 to 190 mm with reducers, connected by flexible duct to a new 4-inch EC centrifugal extractor fan
  • Fan connected to the existing duct outlet, and the redundant shared duct section sealed off
  • 4-inch in-line silencer with additional ducting
  • Restroom extractor replaced with the same 4-inch EC fan
  • False wall and ceiling opened, patched and made good
  • Mitsubishi Electric multi-split and a 24,000 Btu Midea ceiling cassette installed for the café floor
  • Drainage pipe outside the staff toilet fixed, and every unit on a quarterly servicing plan

The result

The room stays fresh for customers, and the fans stay on because nobody can hear them. The café now has one contractor for its cooling, ventilation and servicing.